Schneider Electric 24337, C60n2pc16a 6Ka C Se 16A 2Kut Oto Sig
Main Range of product C60 Range Multi9 product name C60 Product or component type Miniature circuit-breaker Device short name C60N Device application Distribution Poles description 2P Number of protected poles 2 Neutral position Left [In] rated current 16 A at 30 °C network type AC Trip unit technology Thermal-magnetic Curve code C Breaking capacity 20 kA Icu at 130 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 230
Ürün Açıklamaları
Main Range of product C60 Range Multi9 product name C60 Product or component type Miniature circuit-breaker Device short name C60N Device application Distribution Poles description 2P Number of protected poles 2 Neutral position Left [In] rated current 16 A at 30 °C network type AC Trip unit technology Thermal-magnetic Curve code C Breaking capacity 20 kA Icu at 130 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 230
240 V AC 50/60 Hz conforming to EN/IEC 60947-2 3 kA Icu at 400
415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 15 kA Icu at 60 V DC 1P conforming to EN/IEC 60947-2 Suitability for isolation Yes conforming to IEC 60947-2 Complementary Network frequency 50/60 Hz [Ue] rated operational voltage 230
240 V AC 50/60 Hz 400
415 V AC 50/60 Hz 130 V AC 50/60 Hz 230/400 V AC 50/60 Hz Magnetic tripping limit 5
10 x In [Ics] rated service breaking capacity 15 kA conforming to EN/IEC 60947-2 - 130 V AC 50/60 Hz 7
5 kA conforming to EN/IEC 60947-2 - 230
240 V AC 50/60 Hz 6000 A conforming to EN 60898 - 230/400 V AC 50/60 Hz 2
25 kA conforming to EN/IEC 60947-2 - 400
415 V AC 50/60 Hz Limitation class 3 conforming to EN/IEC 60947-2 Contact position indicator Yes Control type Toggle Local signalling ON/OFF indication Mounting mode Clip-on Mounting support 35 mm symmetrical DIN rail 9 mm pitches 4 Height 81 mm Width 36 mm Depth 73 mm Net weight 0
24 kg Mechanical durability 20000 cycles Connections - terminals Tunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid Earth-leakage protection Separate block Environment Standards IEC 60898 EN/IEC 60947-2 Tropicalisation 2 conforming to IEC 60068-1 Relative humidity 95 % at 55 °C Operating altitude 2000 m Ambient air temperature for operation -25…60 °C Ambient air temperature for storage -40…70 °C Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 7
5 cm Package 1 Width 3
6 cm Package 1 Length 8